RZR®-SZZ

Automatic machine RZR®-SZZ is a microprocessor unit for automatic turning on of reserve power supply (ATR/SZR) and automatic return to basic power supply (ARB/APZ) of a switching station 0.4 kV.

Application

Automatic machine RZR®-SZZ ensures constant power supply in networks n/n in public buildings, apartment buildings and industrial establishments. The unit is adopted for operation in a configuration 2 – switches (contactors *), 1 section and 2 power sources.

The unit performs switchings:
• ATR – from AC dump,
• ARB – after voltage return,
• APT – automatic power turning on after unit activation.

Characteristic features

• Manufactured with use of a modern microprocessor RISC type.
• Small dimensions.
• Comfortable and simple maintenance.
• Low power consumption.
• High resistance to interferences in input and output circuits.
• Provided with additional indication of position of switches.

It is possible to:
- set a delay of turning on and off the switches
- have a direct control of commutation elements (switches, contactors),
- monitor switching station status (switches and voltages) by means of LED display,
- block the unit through external contact and key lock,
- change the delay range of turning off and turning on by manufacturer.

Operation

Automatic machine RZR®-SZZ controls the occurrence of two voltages and status of 2 switches. Depending on switch position and voltage occurrence the unit carries out switching procedure which leads to the condition according to the diagram below:

Structure

The automatic unit is located in a PVC housing adopted for mounting on a DIN rail.

The front plate of the unit contains:
• key lock for unit blocking,
• indicator showing the presence of a power supply voltage,
• blocking indicator,
• turning knob for adjustment of turning off and on of switches.

The upper and lower part of the housing has outlets to connect the unit with a controlled system. The housing contains the following main components of the unit:
• power supply,
• output relays,
• separator systems,
• front plate block (signal lights),
• microprocessor system for measurement and control with adjustment of function delay.


Download a catalogue

Basic technical data
Three-phase measurement rated voltage Un 400 V AC, 50 Hz
Rated power voltage Uz AC 230 V
+ 10%, - 20%
Threshold voltage of controlled phases 180 V AC ± 10%
Range of adjustment of boot-time delay (0,05 ÷ 7,5) s
co 0,5 s
Duration of output pulses for control of switches 0,5 s
Deviation of time elements ≤ 1%
Class of time elements with regard to dispersion 1
Additional deviation caused by influence of supply voltage alterations and temperature ± 1%
Working temperature range (-5 ÷ +55)°C
Allowable relative humidity 90%
(without condensation)
Contact capacity:
• maximum start current
• rated current of contact load
– in AC1 category
– in DC1 category
• durable
• maximum voltage of contacts AC/DC
15 A
 
 
6 A by 250 V AC
6 A / 24 V DC
6 A
250 V / 300 V
Rated power consumption ≤ 10 W
Durability of connection of output relays > 0,6 x 105
Dimensions (160 x 90 x 66) mm
Weight ok. 1,0 kg
Protection level IP 40