Application

Single-phase current equalizing autotransformers AZWO are designed to work with main transformers. They are used in the circuits of differential protections of power transformers.

Structure

Autotransformers AZWO have a wound core of RZS type. Core dimensions depend on the parameters of autotransformers. The core windings are impregnated with polyester resins which act as the main insulation.Autotransformers AZWO are provided with 6 terminals, both on a primary and secondary winding. The devices fully comply with the Technical Demands (WT/X.75)


Download a catalogue


Current equalizing autotransformers AZWO
Primary and secondary rated currents secondary current [A]
1
5
primary current [A]
0,495÷9,654
0,712÷17,94
Rated power 10, 20 or 30VA
Accuracy class 10 P
Rated overcurrent number n > 10
Isolation rated voltage 0,5kV/50Hz
Test voltage by secondary current 1A - 4kV/50Hz
5A - 2kV/50Hz
Rated frequency 50Hz
Working temperature range -25°C ÷ +55°C